Product Center

Temperature controlled deluge valve

Temperature controlled deluge valve

product manual

CCC certificate

Inspection Report

1.Description
The temperaturecontrolled deluge valve is an automatic control valve in the automatic sprinkler system. It is a deluge valve that is automatically opened at a constant temperature and can be manually and electrically opened. Mainly used in door openings, windows, fire shutter doors, etc. for fire separation, cooling rain control valves; can also be used for equipment, areas of directional fire separation; and small areas of water spray fire, fire control. The upper interface is connected to the detecting nozzle and the starting solenoid valve and the ball valve.

 

2.Working principle
When the fire water source enters the control chamber from the water inlet, the pressure in the control chamber is greater than the inlet pressure, so that the water inlet is pressed against the seal. When the fire occurs, the temperature sensing nozzle moves, the pressure in the control chamber drops, and the seal assembly moves up. The water flows into the pipe network from the water inlet, and is fired, controlled, fired, and cooled by the open nozzle.

 

3、Model specifications and main technical parameters

Model

Inlet

Outlet

Probe head interface

Length × width × height (mm)

ZSFM32

Rc1¼″

Rc1¼″

Rc½″

200×120×90

ZSFM40

Rc1″

Rc1½″

Rc½″

200×120×90

ZSFM50

Rc2″

Rc2″

Rc½″

230×135×140

ZSFM65

Rc2½″

Rc2½″

Rc½″

230×140×160

ZSFM80

Rc3″

Rc3″

Rc½″

295×195×200

 

3、Model specifications and main technical parameters

Rated working pressure: 1.2MPa

Hydraulic strength test: 2.4MPa for 3min, no leakage

Functional test: Pressure relief opening and upper pressure sealing 0.14MPa~1.32MPa correct operation

Glass ball nominal operating temperature selection: 30 ° C higher than the maximum temperature of the environment

 

4.Design Points

1) The function of the glass ball nozzle in the temperature-controlled deluge valve system is to detect the ambient temperature and start the deluge valve, which itself does not have a fire extinguishing function. The nozzle should be equipped with a protective frame and installed with a special wrench. The distance between the nozzle splashing plate and the top plate is 75-150 mm. It is recommended to use an upright nozzle.

2) The temperature-controlled deluge valve system can also be temperature-controlled, electronically controlled and manually started.

3) The larger the diameter of the temperature-controlled deluge valve, the more the number of nozzles that can be installed. The specific quantities are as follows:

Model

Nozzle K factor

Number of nozzles

ZSFM32

80

4

ZSFM40

6

ZSFM50

10

ZSFM65

14

ZSFM80

22